2776u ORDINANCE NO.2776 AN ORDINANCE AMENDING CHAPTER 16.52 OF THE MOSES LAKE MUNICIPAL CODE ENTITLED "INSTALLATION AND MAINTENANCE OF AUTOMATIC FIRE EXTINGUISHING SYSTEMS" THE CITY COUNCIL OF THE CITY OF MOSES LAKE,WASHINGTON ORDAINS AS FOLLOWS: Section 1.Chapter 16.52 of the Moses Lake Municipal Code entitled "Installation and Maintenance of Automatic Fire Extinguishing Systems"is amended as follows: 16.52.040 Fire Extinguishing Systems: A.Where Reguired:In addition to the locations reguired to install automatic sprinkler systems bythe currentlyadopted State FireCode in Group R-1 and R-2 occupancies,locationswhich are twelve thousand five hundred (12,500)sguare feet in total area,or larger,are reguired to installautomatic sprinklers throughout,including the attic:except,Group Roccupancies twelve thousand five hundred (12,500)sguare feet in total area,or larger, with an NFPA 13R automatic fire sprinkler system,and that are eguipped with a Class III standpipe system in accordance with NFPA Standard 14 shall be exempt from the reguirement to install attic sprinklers. B.Sprinkler System Alarms:When serving more than twenty (20)sprinklers,automatic sprinkler systems shall be supervised by an approved central proprietary or remote station service or a local alarm which will give an audible signal at a constantly attended location. C. Fire Department Connections:All newly installed fire department connections shall be eguipped with Knox locking caps. D. Fire DepartmentConnection Location:On all new construction and in buildings retro-fitted with automatic fire sprinkler systems,Fire Department connections shall be located not less than fortyfeet (40') from the protected building at a location approved by the Fire Marshal:except, where practical difficulties preclude the remote placementof Fire Department connections,the Fire Chief may grant a waiver and authorize placement at a location reviewed and approved by the Fire Marshal. E. Fire Department Connection Reguirements:The topof the Fire Department connection shall not be more than forty-four inches(44") nor less than thirty-six inches (36")above grade.All Fire Department connection riser piping shall be painted red from grade to just below the threaded connection for the hose cap. F.Exterior Strobe Reguired:Buildings with sprinkler risers at separate locations within the building envelope shall be eguipped with an exterior visual strobe device adjacent to the exterior water flow bell or alarmforeach individual system within the building. Section 2.This ordinance shall take effect and be in force five (5)days afterits passage and publication of its summary as provided by law. Adopted bythe City Counciland signed byits Mayor on July28,2015. ATTEST: APPROVED AS TO FORM: Dick Deane,Mayor W.RobertTaylor,FirranQe Director 'rL><rnf/l f/lAJnf; Katherine L.Kenison,City_Attofney